Vue de la page 65
McQuay Service Guide Book
65
Chilled Water Fan Coil Unit
Model Board Handset
WM 005 – 025FW, 301W W1V3 G7 / SLM3 / Netware 3
CK 020 – 050AW/AWH W1V3 G7 / SLM3 / Netware 3
CK 015 – 025BW W1V3 G7 / SLM3 / Netware 3
CK 010 – 020CW W1V3 G7 / SLM3 / Netware 3
CE 020 – 050DW/CBW W1V3 G7 / SLM3 / Netware 3
CC 010 – 060CW W1V3 SLM3 / Netware 3
SB 075 – 150BW N/A No Controller
Self Diagnostic Table – W1V3
Fault Indication POWER LED / COOL LED Other LEDs Seven Segments
Room sensor missing Blinks 4 times FAN blinks E1 blinking
Indoor coil sensor missing Blinks 4 times SLEEP blinks E2 blinking
Pump fault Blinks 2 times COOL & FAN blink E6 blinking
Pipe water temperature poor Blinks 3 times COOL & DRY blink E4 blinking
Pipe water temperature fault Blink 1 time COOL blinks E5 blinking
Model Board Handset
WM 007 – 025GW W2 G17 / SLM3 / Netware 3
WM 301W W2 G17 / SLM3 / Netware 3
CK 020 – 050AW/AWH W2 G17 / SLM3 / Netware 3
CK 015 – 025BW W2 G17 / SLM3 / Netware 3
CK 010 – 020CW W2 G17 / SLM3 / Netware 3
CE 007 – 015CBW W2 G17 / SLM3 / Netware 3
CE 020 – 050DW W2 G17 / SLM3 / Netware 3
CE 015 – 025EW W2 G17 / SLM3 / Netware 3
CC 010 – 060CW W2 SLM3 / Netware 3
SB 075 – 150BW N/A No Controller
Self Diagnostic Table – W2
Fault Indication COOOL LED Seven Segments
Room sensor error (short/open) Blink 1 time E1
Pipe water sensor error (short/open) Blink 2 times E2
Water pump error Blink 6 times E6
Pipe water temperature fault Blink 5 times E5
Window open activated* Blink 3 times -
Antifreeze mode activated* Blink 7 times -
Load shedding activated* Blink 8 times -
*Applicable for 4 pipes applications only.