McQuay M5MAC Guide de dépannage Page 38

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 90
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 37
McQuay Service Guide Book
37
6.5 Sequential Controller
It is allowed to configure the controller to suit individual’s need with details below:
1. Models
For each type, there are 3 models for the control to configure into.
Dip switch 1 Dip switch 2 Dip switch 5
a. Cooling (SQCn) Off Off Off
b. Heatpump + no heater (SQHn0) On Off Off
c. Heatpump + 1 heater (SQHn1) Off On Off
d. Heatpump + 2 heater (SQHn2) On On Off
e. Auto heatpump + no heater (SQHn0) On Off On
f. Auto heatpump + 1 heater (SQHn1) Off On On
g. Auto heatpump + 2 heater (SQHn2) On On On
n denotes number of compressor(s)
where the postfix number indicates number of compressor(s).
2. Stage Differential Temperature
Differential temperature is the temperature difference between turning on or off 1 compressor to
another compressor in thermostat cycle.
The stage differential temperature can be selected from the range shown below:
Dip switch 3 Dip switch 4
a. Default Off Off
b. 0.5°C On Off
c. 1.0°C Off On
d. 1.5°C On On
Note that 1.5°C only valid for 2 and 3 compressors model. For 4 compressors model, maximum
allowed is 1.0°C.
The default differential temperature is base on number of compressor model, the setting is as below:
Model Diff. Temperature
1 compressor Not. Applicable
2 compressors 0.5°C
3 compressors 1.0°C
4 compressors 1.5°C
3. Hot Keep Option
Dip switch 6
a. Fan off Off
b. Fan on On
45. Operating Modes
The system has 4 operating modes to select with respect to each model selection:
Model Auto Cool Heat Fan
SQCn - X - X
SQHnh - X X X (Dip switch 5 = off)
SQHnh X X X X (Dip switch 5 = on)
Where x denotes modes available
n = number of compressor(s)
h = number of heater(s)
Vue de la page 37
1 2 ... 33 34 35 36 37 38 39 40 41 42 43 ... 89 90

Commentaires sur ces manuels

Pas de commentaire