McQuay M5LCX Spécifications Page 42

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 51
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 41
40
ii ) Diagnosis of Refrigerant Circuit / Application
There might be some causes where the unit starts running but does not perform satisfactorily, i.e. insufficient
cooling. Judgement could be made by measuring temperature difference of indoor unit’s intake and discharge
air as well as running current.
Satisfactory operation with temperature difference of air intake & discharge of indoor unit
8°C to 13°C. *
( * value is for reference only )
Vue de la page 41
1 2 ... 37 38 39 40 41 42 43 44 45 46 47 ... 50 51

Commentaires sur ces manuels

Pas de commentaire