McQuay MLCV Spécifications

Naviguer en ligne ou télécharger Spécifications pour Climatiseurs à système divisé McQuay MLCV. McQuay MLCV Specifications Manuel d'utilisatio

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 144
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs

Résumé du contenu

Page 1 - Split Systems

MCM-2009Ceiling ExposedSplit SystemsCatalog MCM 020D/DR MCM 025D/DR MCM 030D/DR MCM / M5CM 040D/DR MCM / M5CM 050D/DR MCM / M5CM 062C/CRModels:

Page 2 - Table of Contents

Application InformationOperating RangeEnsure the operating temperature is in allowable range.Cooling only!Caution :The use of your air conditioner out

Page 3 - Nomenclature

1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151.98Electric

Page 4 - LC 020 C R 5 M

1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151.99Electric

Page 5 - LC 030 C R 4 M

Electrical Data - Cooling only (R410A)1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TE

Page 6 - Product Line Up

1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151.101Electri

Page 7 - MLC-C Series Product Line Up

Wiring Diagrams102Cooling onlyIndoor UnitModel : MCM 020 / 025DOutdoor UnitModel : MLC 018 / 020 / 025C

Page 8 - M5LC-C Series Product Line Up

Indoor UnitModel : MCM 030D103Outdoor UnitModel : MLC 028C

Page 9 - Features

104Indoor UnitModel : MCM 030DIndoor UnitModel : MLC 030C

Page 10 - Caution :

105Indoor UnitModel : MCM 040DOutdoor UnitModel : MLC 035 / 040C (1 Phase)

Page 11 - MODEL: MCM 025D – MLC 025C

106Indoor UnitModel : MCM / M5CM 040D, MCM 050CDOutdoor UnitModel : MLC / M5LC 040C, M5LC 035C , MLC 050C (3 Phase)

Page 12 - MCM 062C – MLC 061C

107Indoor UnitModel : M5CM 040DOutdoor UnitModel : M5LC 035C (1 Phase)

Page 13 - M5CM 062C – M5LC 061C

Refrigerant Circuit DiagramModel: MCM 020D – MLC 018 / 020C MODEL: MCM 025D – MLC 025C9

Page 14 - MCM 050DR - MLC 050CR

Indoor UnitModel : M5CM 040D108Outdoor UnitModel : M5LC 040C (1 Phase)

Page 15 - M5CM 062CR – M5LC 061CR

Indoor UnitModel : M5CM 050COutdoor UnitModel : M5LC 050C109

Page 16 - G7 Remote Controller

110Indoor UnitModel : MCM / M5CM 062COutdoor UnitModel : MLC / M5LC 061C

Page 17

111Indoor UnitModel : MCM 020 / 025DROutdoor UnitModel : MLC 018 / 020 / 025CR Heatpump

Page 18 - Wired Remote Control - SLM

Indoor UnitModel : MCM 030DROutdoor UnitModel : MLC 028CR112

Page 19 - Phsae Sequencer

113Indoor UnitModel : MCM 030 / 040DROutdoor UnitModel : MLC 030 / 035/ 040CR (1 Phase)

Page 20 - Installation

114Indoor UnitModel : MCM 030 / 040/ 050DROutdoor UnitModel : MLC 030/ 040/ 050CR (3 Phase)

Page 21 - MCM-D MCM 062C

Indoor UnitModel : MCM / M5CM 040DROutdoor UnitModel : M5LC 035CR (1 Phase)115

Page 22 - Figure D

Indoor UnitModel : M5CM 040DR116Outdoor UnitModel : M5LC 040CR (1 Phase)

Page 23

Indoor UnitModel : M5CM 040DROutdoor UnitModel : M5LC 035 / 040CR (3 Phase)117

Page 24 - Figure J

Model : MCM 030D – MLC 028CModel : MCM 030D – MLC 030CMCM 040D – MLC 035 / 040CMCM 050D – MLC 050CMCM 062C – MLC 061C10

Page 25 - Installation Clearance

Indoor UnitModel : M5CM 050DR118Outdoor UnitModel : M5LC 050CR

Page 26 - (3) Refrigerant Piping

119Indoor UnitModel : MCM 062CROutdoor UnitModel : MLC 061CR

Page 27 - (5) Vacuuming and Charging

Indoor UnitModel : M5CM 062CROutdoor UnitModel : M5LC 061CR120

Page 28 - (6) Additional Charge

Outdoor UnitModel : MLC 030C (Cooling only)50Hz / 1 Phase / 220 ~ 240V121High Ambient UnitOutdoor UnitModel : MLC 040 / 050C (Cooling only)50Hz / 3

Page 29

122High Ambient UnitOutdoor UnitModel : MLC 030CR (Heatpump)50Hz / 1 Phase / 220 ~ 240VOutdoor UnitModel : MLC 040 / 050CR (Heatpump)50Hz / 3 Phase /

Page 30

Servicing and MaintenanceWarning: Disconnect from main supply before servicing the air conditioner.The unit is designed to give long life operation

Page 31 - (6) Overall Checking

The design of the MLC outdoor series allows servicing to be carried out readily and easily. The removal of the topside, front and back panel make almo

Page 32 - Sound Data

TTTTTrrrrroubouboubouboubleshootingleshootingleshootingleshootingleshooting125When a malfunction of the air conditioner unit is detected, immediately

Page 33 - MCM 025D/DR NC CURVES

Diagnostic GuidelinesBy means of pressure readings:Data Pressure Circuit Too low A little low Normal A little high Too high Probable cause High si

Page 34 - MCM / M5CM 040D/DR NC CURVES

By Means Of Diagnostic Flow Chart :Generally, there are two kinds of problems, i.e. starting failure and insufficient cooling/heating. “Starting failu

Page 35 - MCM / M5CM 062C/CR NC CURVES

11Model : M5CM 040D – M5LC 035 / 040CM5CM 050D – M5LC 050CM5CM 062C – M5LC 061CModel : MCM 020DR – MLC 018 / 020CR

Page 36 - Engineering and Physical Data

128ii ) Diagnosis of Refrigerant Circuit / ApplicationThere might be some causes where the unit starts running but does not perform satisfactorily, i.

Page 37

129Satisfactory operation with temperature difference of air intake & discharge of indoor unit14°C to 20°C. *( * value is for reference only )Rest

Page 38

Exploded View and Parts ListModel : MCM 020 / 025 D/DR130No Description Part No. No Description Part No.1 Top Panel R01014022475 17 Side Frame Assy.,

Page 39

Model : MCM 030 D/DR131No Description Part No. No Description Part No.1 Bracket Hanger, Left R01014032844 16 Drain Hose Assy. R501240251132 Control Bo

Page 40

Model : MCM / M5CM 040 / 050 D/DR132No Description Part No. No Description Part No.1 Bracket Hanger, Left R01014032844 17 Air Intake Grille Frame Hold

Page 41

Model : MCM / M5CM 062 C/CR133No Description Part No. No Description Part No.1 Top Back Panel R50015039175 15 Terminal Box R010140219612 Coil Holder

Page 42

134Model : MLC 018 / 020CNo Description Part No No Description Part No1 Assy. Base Pan R50014078281 13 Terminal Cover Panel R010140708382 Assy. Outdoo

Page 43

135Model : MLC 025 / 028CNo Description Part No No Description Part No1 Assy. Base Pan R50014073884 13 Terminal Cover Panel A010140708382 Assy. Outdoo

Page 44

Model : MLC 020CR136No Description Part No No Description Part No1 Assy. Base Pan R50014078281 13 Terminal Cover Panel R010140708382 Assy. Outdoor Coi

Page 45

Model : MLC 025 / 028CR137No Description Part No No Description Part No1 Assy. Base Pan R50014073884 14 Assy. Control Panel2 Assy. Outdoor Coil MLC 02

Page 46

12Model : MCM 025DR - MLC 025CRMCM 030DR - MLC 028CR Model : MCM 030DR - MLC 030CRMCM 040DR - MLC 040CRMCM 050DR - MLC 050CR

Page 47

Model: MLC 030 / 040C/CRNo Description Part No No Description Part No1 Assy. Base Pan R50014053238 11 Bracket, Fan Motor R010140532322 Assy. Flare Val

Page 48

139Model: M5LC 035/040C/CR1) ALL SPECIFICATIONS ARE SUBJECT TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICENo Description Part No No Description Pa

Page 49

140Model : MLC 050 / 061CRNo Description Part No No Description Part No1 Assy. Base Pan R50014053238 11 Bracket, Fan Motor2 MLC 050C/CR MLC 050C/CR R0

Page 50 - Components Data (R22)

141Model : M5LC 050/061C/CR1) ALL SPECIFICATIONS ARE SUBJECT TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICENo Description Part No No Description P

Page 51

291© 2009 McQuay International +1 (800) 432-1342 www .mcquay. com Products manufactured in an ISO certified facility. This document contains the mo

Page 52

13Model : M5CM 040DR – M5LC 035 / 040CRM5CM 050DR – M5LC 050CRM5CM 062CR – M5LC 061CRModel : MCM 062CR – MLC / M4LC 061CR

Page 53

G7 Remote Controller14

Page 54

COOLDRYHEATMEDHIGHAUTOMODETEMPSENSORON/OFFSLEEPLOWTIMER82593641FANFAN ON/OFFTEMPSLEEPTIMER MODE7123456107SWINGSWINGFANSLM AC-5300 (OPTIONAL)1. “ON/OFF

Page 55

Operating State and Fault TableWireless Remote Controller - HandsetCooling: LED Indicator Light Display Heatpump : LED Indicator Light Displ

Page 56

Phsae SequencerThe unit with Scroll Compressor can only rotate in one direction. For this reason, a protective device (phasesequencer) is fitted to pr

Page 57

Nomenclature ... 1 - Product Line UpFeatures

Page 58

InstallationSharp edges and coil surfaces are potential injury hazard. Avoid from contact with them.(1) Installation of Outdoor UnitPreliminary Site S

Page 59

Please ensure that the following steps are taken :• Check the gradient for drainage flow as recommended in Figure B.• Provide clearance for easy servi

Page 60 - Component Data (R410A)

MCM 062C • Provide the installation space as shown in Figure D. MCM-D MCM 062CFigure CFigure D20

Page 61

Installation - Ceiling Exposed TypeSTEP 1Remove air intake grille, side panel, side close-up and hanger bracket from the unit; see Fig E.Figure ESTEP

Page 62 - Component Data (R22)

Installation - Floor Standing TypeSTEP 1Remove air intake grille, side panel, side close-up and side panel from the unit; see Fig E.STEP 2Position th

Page 63

23(2) Installation of Outdoor UnitAs condensing temperature rises, evaporating temperature rises and cooling capacity drops. In order to achieve maxim

Page 64 - Safety Devices

(3) Refrigerant PipingMaximum Pipe Length and Maximum Number of Bends• When the pipe length becomes too long, both the capacity and reliability drop.

Page 65

4) WiringELECTRICAL CONNECTIONS• Wiring regulations on wire diameters differ from country to country. Please refer to your LOCAL ELECTRICALCODES for f

Page 66

Diagram shows typical charging method.26Note : R407C - Fix filter dryer R22 - Nil R410A - Nil(6) Additional Charge• The refrigerant

Page 67

Special Precautions When Dealing with Refrigerant R410A Unit1) What is New Refrigerant R410A?R410A is a new HFC refrigerant which does not damage the

Page 68 - Performance Data

Nomenclature C A F A - Model Type R : Heatpump Omitted if Cooling Only Series C : C Series D : D Series Capacity 040 : 40,000 Btu/h Model Name CM

Page 69

d) When charging R410A, ensure that only liquid is being withdrawn from the cylinder or can. This is toensure that only the original composition of R4

Page 70

(6) Overall Checking• Ensure the following, in particular:1. The unit is mounted solidly and rigid in position.2. Piping and connections are leak proo

Page 71 - Total capacity, TC

Sound Data30Overall Noise125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz A(dBA) CriteriaHigh 45 46 47 46 41 38 29 50 45Medium 42 43 45 42 38 34 24 47 41Low 36 3

Page 72 - ID DB°C ID WB°C

31MCM 020D/DR NC CURVESMCM 025D/DR NC CURVES

Page 73

32MCM30D/DR NC CURVESMCM / M5CM 040D/DR NC CURVES

Page 74 - ID WB°CID DB°C

33MCM / M5CM 050D/DR NC CURVESMCM / M5CM 062C/CR NC CURVES

Page 75

Engineering and Physical DataGeneral Data - Cooling only (R22)341) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE

Page 76

351) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151.3) NOMIN

Page 77

361) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151.3) NOMIN

Page 78

371) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151.3) NOMIN

Page 79

Outdoor2 O A P C A - Model Type R : Heatpump Omitted if Cooling Only Series C : C series Capacity 020 : 20,000 Btu/h Model Name LC : Single Split Co

Page 80

381) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151.3) NOMIN

Page 81

39General Data - Heat Pump (R22)1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED A

Page 82

401) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151.3) NOMIN

Page 83

411) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151.3) NOMIN

Page 84

421) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151.3) NOMIN

Page 85

431) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151.3) NOMIN

Page 86

44General Data - Cooling Only (R410A)M5LC 035C M5LC 040CBtu/h 33000 / <33300> 38500 / <38500>W 9670 / <9670> 11280 / <11280>W

Page 87

45General Data - Cooling Only (R410A)1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TES

Page 88

461) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151

Page 89

471) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151.

Page 90 - Heating Mode

Outdoor3 G E F A - Model Type R : Heatpump Omitted if Cooling Only Series B : B Series C : C Series Capacity 030 : 30,000 Btu/h Model Name LC : Sin

Page 91

Components Data (R22)1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.48MLC 018C MLC 020Cmm/inmm/inmm/incm3 / fl

Page 92 - All dimension in mm

1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.49Components Data (R22)mm/inmm/inmm/incm3 / fl.oz.mm/inmm/inmm/

Page 93 - Model : MCM 062C/CR

1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.50Components Data (R22)MLC 028C MLC 030Cmm/inmm/inmm/in457 / 18

Page 94 - MLC 020 / 025 / 028C/CR

1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.51Components Data (R22)MLC 035C MLC 040Cmm/inmm/inmm/inMINERAL

Page 95 - Model : MLC / M5LC 061C/CR

1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.52Components Data (R22)MCM 050D MCM 062CMLC 050C MLC 061CABS AL

Page 96 - Electrical Data

1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.53Components Data (R22)MLC 018CR MLC 020CRmm/inmm/inmm/incm3 /

Page 97

1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.54Components Data (R22)mm/inmm/inmm/incm3 / fl.oz.mm/inmm/inmm/

Page 98

1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.55Components Data (R22)MLC 028CR MLC 030CRmm/inmm/inmm/in457 /

Page 99

1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.56Components Data (R22)MLC 035CR MLC 040CRmm/inmm/inmm/inMINERA

Page 100

1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.57Components Data (R22)MCM 050DR MCM 062CRMLC 050CR MLC 061CRAB

Page 101

Product Line UpIndoor UnitMCM-D Series Product Line Up (R22)Indoor UnitM5CM-D Series Product Line Up (R410A)4ControlL208A PCBSLMG7 HandsetCE MarkW/out

Page 102

Component Data (R410A)1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.58M5LC 035C M5LC 040Cmm/inmm/inmm/inSCROL

Page 103

1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.59Component Data (R410A)M5CM 050D M5CM 062CM5LC 050C M5LC 061C4

Page 104 - Wiring Diagrams

1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.60Component Data (R22)MLC 035CR MLC 040CRmm/inmm/inmm/inSCROLL

Page 105 - Model : MLC 028C

1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.61Component Data (R410A)M5CM 050DR M5CM 062CRM5LC 050CR M5LC 06

Page 106 - Model : MLC 030C

62Safety Devices1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.MLC 018C MLC 020CN/A N/AOPEN kPa / psiN/A N/ACL

Page 107 - Model : MCM 040D

631) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.Safety DevicesMCM 050D MCM 062CMLC 050C MLC 061CNC NCOPEN kPa

Page 108

641) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.Safety DevicesMLC 035CR MLC 040CRNC NCOPEN kPa / psi2937 / 42

Page 109 - Model : M5LC 035C (1 Phase)

651) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.Safety DevicesM5LC 035C M5LC 040CNC NCOPEN kPa / psi2937 / 42

Page 110 - Model : M5LC 040C (1 Phase)

Performance DataInterpolation and Extrapolation method can be used to get the total capacity, TC and sensible capacity, SC atthose temperatures which

Page 111 - Model : M5LC 050C

67Details:1st Step:To obtain the Total capacity and Sensible capacity for(a) Indoor Condition: 24°C DB, 15°C WBOutdoor Condition: 35°C DBTotal capaci

Page 112 - Model : MLC / M5LC 061C

Outdoor UnitMLC-C Series Product Line Up5ellirGebuT .paCVXTniF dloGtiK tneibmA hgiHtiK tneibmA woLrotcatnoChctiwS erusserP hgiHhctiwS erusserP woLWS .

Page 113 - Heatpump

682nd Step:To obtain the Total capacity and Sensible capacity for(a) Indoor Condition: 23°C DB, 15°C WB Outdoor Condition: 35°C DBTotal capacity,

Page 114 - Model : MLC 028CR

693rd Step:To obtain the Total capacity and Sensible capacity for(a) Indoor Condition: 23°C DB, 15°C WB Outdoor Condition: 37°C DBTotal capacity,

Page 115 - Model : MCM 030 / 040DR

R22 Models(Cooling only)Model : MCM 020D / MLC 018CModel : MCM 020D / MLC 020B70TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW)

Page 116 - Model : MCM 030 / 040/ 050DR

R22 Models(Cooling only)Model : MCM 025D / MLC 025CModel : MCM 030D / MLC 028C71TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW)

Page 117 - Model : M5LC 035CR (1 Phase)

72R22 Models(Cooling only)Model : MCM 030D / MLC 030CModel : MCM 040D / MLC 035CTC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW)

Page 118 - Model : M5LC 040CR (1 Phase)

73R22 Models(Cooling only)Model : MCM 040D / MLC 040CModel : MCM 050D / MLC 050CTC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW)

Page 119

R22 Models(Cooling only)Model : MCM 062C / MLC 061C74TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW)1517.094 10.28

Page 120 - Model : M5LC 050CR

R22 Models(Heatpump)Model : MCM 020DR / MLC 018CRCooling ModeHeating Mode75TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(k

Page 121 - Model : MLC 061CR

76R22 Models(Heatpump)Model : MCM 020DR / MLC 020CRCooling Mode Heating ModeTC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(

Page 122 - Model : M5LC 061CR

77R22 Models(Heatpump)Model : MCM 025DR / MLC 025CRCooling Mode Heating ModeTC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(k

Page 123

Outdoor UnitM5LC-C Series Product Line Up6GrilleCap. TubeTXVGold FinHigh Ambient KitLow Ambient KitContactorHigh Pressure SwitchLow Pressure SwitchNan

Page 124

78R22 Models(Heatpump)Model : MCM 030DR / MLC 028CRCooling Mode Heating ModeTC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(k

Page 125 - Servicing and Maintenance

79R22 Models(Heatpump)Model : MCM 030DR / MLC 030CRCooling Mode Heating ModeTC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(

Page 126 - For MLC Outdoor Models

80R22 Models(Heatpump)Model : MCM 040DR / MLC 035CRCooling Mode Heating ModeTC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(

Page 127

81R22 Models(Heatpump)Model : MCM 040DR / MLC 040CRCooling Mode Heating ModeTC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(

Page 128 - Diagnostic Guidelines

82R22 Models(Heatpump)Model : MCM 050DR / MLC 050CRCooling Mode Heating ModeTC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(

Page 129

83R22 Models(Heatpump)Model : MCM 062CR / MLC 061CRCooling Mode Heating ModeTC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(

Page 130

84R410A Models(Cooling only)Model : M5CM 040D / M5LC 035CModel : M5CM 040D / M5LC 040CTC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) S

Page 131 - 14°C to 20°C. *

85R410A Models(Cooling only)Model : M5CM 050D / M5LC 050CModel : M5CM 062C / M5LC 061CTC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) S

Page 132 - Exploded View and Parts List

86R410A Models(Heatpump)Model : M5CM 040DR / M5LC 035CRCooling ModeHeating ModeTC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) T

Page 133 - Model : MCM 030 D/DR

87R410A Models(Heatpump)Model : M5CM 040DR / M5LC 040CRCooling ModeHeating ModeTC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) T

Page 134

FeaturesUltra Slim New Stylish Design ProfileThis unit is contemporary in design and match even the most up to date interior decor. The slim, roundpro

Page 135 - Model : MCM / M5CM 062 C/CR

88R410A Models(Heatpump)Model : M5CM 050DR / M5LC 050CRCooling ModeHeating ModeTC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) T

Page 136 - Model : MLC 018 / 020C

89R410A Models(Heatpump)Model : M5CM 062CR / M5LC 061CRCooling ModeHeating ModeTC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) T

Page 137 - Model : MLC 025 / 028C

Dimensional DataIndoor UnitModel : MCM - D SERIES (Cooling only and Heatpump)All dimension in mm90MODEL MCM 020D/DR MCM 025D/DR MCM 030D/DR MCM

Page 138 - Model : MLC 020CR

Model : MCM 062C/CR91All Dimension in mmMCM A(GRILL) B C D E F G H I J K L O T X 062C 1750 40 36 1930 1830 680 352 292 285 140 1880 250 126 13

Page 139 - Model : MLC 025 / 028CR

Outdoor UnitModel : MLC 018C/CR MLC 020 / 025 / 028C/CRNote : Dimension in mm92FOR 25 / 28C/CR ONLYMODEL A B C

Page 140 - Model: MLC 030 / 040C/CR

Model : MLC 030 / 035 / 040 / 050C/CR M5LC 035 / 040 / 050C/CR931030.0746.5141.550.085.040.040.0320.0400.0488.0448.0850.025.0Model : MLC / M5LC

Page 141 - Model: M5LC 035/040C/CR

Electrical DataElectrical Data - Cooling Only (R22)1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS

Page 142 - Model : MLC 050 / 061CR

1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151.95Electric

Page 143 - Model : M5LC 050/061C/CR

1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151.96Electric

Page 144 - 2009 McQuay International

Electrical Data - Heat Pump (R22)1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED