Vue de la page 24
Catalog 1301 / Page 25 of 32
Wiring Diagrams
3– Jumper Placement to Select
Controller Type:
A Place jumper across LUI to select unit mounted
touchpad (Local User Interface).
B Place jumper across T’STAT to select
remote, wall mounted programmable, or non-
programmable thermostat.
3
2
1
Jumper Placement Detail
C
A
B
A
B
A
Wiring Diagram Legend
CT = Control Transformer
CM = Compressor Motor
IFM = Indoor Fan Motor
OFM = Outdoor Fan Motor
OCS = Outdoor Coil Sensor
OAS = Outdoor Air Sensor
ICS = Indoor Coil Sensor
IAS = Indoor Air Sensor
LUI = Local User Interface
REV = Reversing Valve
EHC = Electric Heat Contactor
Standard (Non-Programmable) Digital Control
1– Jumper Placement to Select
System Module (See Jumper Detail)
A Place jumper across AC/E to select Air Conditioner
with Electric Heat.
B Place jumper across HP to select Heat Pump
C Place jumper across HP/E to select Heat Pump
with Electric Back-up Heat.
2– Jumper Placement to Select Fan Control
A When in Fan Cycle Mode, fan operates for 2
minutes – Place jumper across 10, 20, 30, or
1 HR to select fan cycle off minutes which will be
overridden by the room temperature.