Installation Clearance
Single Condensing Unit Installation
Outdoor units must be installed such that there is no short circuit of the hot discharge air or obstruction to smooth air
flow. Select the coolest possible place where intake air should not be hotter than the outside temperature (max 45 °C).
All Models A B C D
Minimum Distance 300 mm 1000 mm 300mm 500mm
NOTE :- (1) If any obstacle is higher than 2m, or if there is any obstruction at the upper part of the unit, allow more space
than indicated in the table above.