Vue de la page 21
20
MODEL : MWM 030FR / MLC 030CR
Indoor DB Indoor WB Capacity Outdoor DB, ° C
° C ° C kW 19.4 25 30 35 40 46 50 52 54
26.7 13.9 TC
7.491 7.228 6.994 6.759 6.435 6.097 5.833 5.690 5.540
SC
7.444 7.191 6.965 6.740 6.416 6.079 5.817 5.674 5.524
15 TC
8.152 7.798 7.482 7.166 6.822 6.464 6.184 6.033 5.873
SC
6.887 6.734 6.597 6.461 6.151 5.828 5.576 5.439 5.295
18 TC
9.955 9.352 8.813 8.275 7.878 7.464 7.142 6.967 6.782
SC
5.368 5.487 5.594 5.701 5.427 5.142 4.920 4.799 4.672
19.4 TC
10.796 10.077 9.435 8.792 8.371 7.931 7.588 7.402 7.206
SC
4.659 4.906 5.126 5.346 5.090 4.822 4.614 4.501 4.382
20 TC
11.156 10.395 9.714 9.034 8.601 8.149 7.797 7.606 7.404
SC
4.355 4.605 4.828 5.051 4.808 4.556 4.359 4.252 4.140
22 TC
12.358 11.454 10.647 9.840 9.368 8.876 8.492 8.284 8.065
SC
3.343 3.603 3.835 4.067 3.872 3.668 3.510 3.424 3.333
24 TC
13.560 12.514 11.579 10.645 10.135 9.602 9.187 8.962 8.725
SC
2.330 2.600 2.841 3.083 2.935 2.781 2.661 2.595 2.527
HIGH AMBIENT
All the data above are based on 26.7°C entering DB. To obtain data for different entering DB, please use the formula below :
Sensible capacity (EDB) = Sensible capacity (26.7) + 1.23 x L/s x (1 - BPF) ( EDB - 26.7 ) / 1000
Where, BPF = Bypass factor
EDB = Entering dry bulb temperature, ° C
MWM 030FR
MLC 030CR
Bypass Factor
0.37