McQuay MWMV Spécifications Page 4

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 27
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 3
Specifications
MODEL
MWV015A MWV015AR MWV020A MWV020AR MWV025A MWV025AR
COOLING CAPACITY
Btu/h
14330 19110 23890
HEATING CAPACITY
Btu/h
- 15360 - 20478 - 25600
COOLING W 4200 5600 7000
POWER INPUT
HEATING W - 4500 - 6000 - 7500
POWER SOURCE V/Ph/Hz 220 - 240 / 1 / 50 220 - 240 / 1 / 50 220 - 240 / 1 / 50
EER 4.2 3.5 3.9
COP - 4 - 3.5 - 3.85
ROW / FIN PER INCH 3 / 14 3 / 14 3 / 12
FACE AREA m
2
0.183 0.183 0.267
POWER INPUT W 103 215 191
Depth mm 178 178 254
FAN
Width mm 178 178 203
CFM 440 600 740
AIR FLOW
L/s 208 283 347
GPM 3.48 4.44 5.7
WATER FLOW
L/s 0.222 0.305 0.361
WATER PRESSURE DROP mH
2
O 1.3 1.5 1.7
WATER CONNECTIONS FPT 3/4
CONNECTIONS I.D. mm 19.05
OPERATING kg 93 95 115
WEIGHT
SHIPPING kg - - 150
Rated in accordance with ANSI/ARI Standard 320-1998
MODEL MWV030A MWV030AR MWV040A MWV040AR MWV050A MWV050AR
COOLING CAPACITY Btu/h 30720 37540 47780
HEATING CAPACITY Btu/h - 34130 - 42660 - 52900
COOLING W 9000 11000 14000
POWER INPUT
HEATING W - 10000 - 12500 - 15500
POWER SOURCE V/Ph/Hz 220 - 240 / 1 / 50 380 - 415 / 3 / 50 380 - 415 / 3 / 50
EER 3.7 - -
COP - 3.7 - -
ROW / FIN PER INCH 3 / 13 3 / 14 3 / 14
FACE AREA m
2
0.267 0.315 0.315
POWER INPUT W 261 275 473
Depth mm 254 254 254
FAN
Width mm 203 254 254
CFM 940 1176 1470
AIR FLOW
L/s 444 555 694
GPM 6.97 - -
WATER FLOW
L/s 0.222 0.305 0.361
WATER PRESSURE DROP mH
2
O 2 2.5 3.5
WATER CONNECTIONS FPT 3/4
CONNECTIONS I.D. mm 19.05
OPERATING kg 125 - -
WEIGHT
SHIPPING Kg 160 - -
Rated in accordance with ANSI/ARI Standard 320-1998
Notes:
1. a) EER = Energy Efficiency Ratio
b) COP = Coefficient of Performance
c) L/s = Liters per second
2. Nominal cooling and heating capacity are based on the conditions below
a) Cooling Capacity is based on 26.7°C (80°F) (DB), 19.4°C (67°F) (WB) entering air temp and 29.6°C (85°F)entering, 35°C (95°F) leaving water
temp
b) Heating Capacity is based on 21.1°C (70°F) (DB) entering air temp and 21.1°C (70°F) entering water temp
3. All specifications are subjected to change by manufacture without prior notice.
Page 3
Vue de la page 3
1 2 3 4 5 6 7 8 9 ... 26 27

Commentaires sur ces manuels

Pas de commentaire