Design & Installation Guide For McQuay MDS Multi SystemEngineered for flexibility and performance.TM
-10-Design & installation Guide For McQuay MDS Multi System1.3 Main Features1.3.1 Wide Range and Stepless Capacity Modulation Wide capacity modula
-100-Design & installation Guide For McQuay MDS Multi SystemMediumCNI connected electronic expansion valveK2J2J1MCUDIP switchDIP switchAC220NRese
-101-Design & installation Guide For McQuay MDS Multi SystemDescription of controller hardware Input port:The system contains 5 test ports designe
-102-Design & installation Guide For McQuay MDS Multi SystemJ2 settings (1: ON: 0: OFF)D1 D5 indicate the local address during intercommunication:
-103-Design & installation Guide For McQuay MDS Multi SystemDIP switch settingNote: 1: 1: ON, 0: OFFS1 (1~2)S1 3~8 indicate the number of connecte
-104-Design & installation Guide For McQuay MDS Multi SystemS2 (4~8) addresses of the outdoor unitAddress No. 4 5 6 7 8000000100001200010300011400
-105-Design & installation Guide For McQuay MDS Multi System5.2 Trial Run Precautions Power up the system 12 hours while you run it for the first
-106-Design & installation Guide For McQuay MDS Multi System6.1 User Guide6.1.1 Responsibilities and ObligationsThis product is covered under MacQ
-107-Design & installation Guide For McQuay MDS Multi System6.2 Servicing and Maintenance Caution: Do not use or place inflammable and explosive
-108-Design & installation Guide For McQuay MDS Multi System Fan motorThis component requires only a little care. As the motor is lubricated and s
-109-Design & installation Guide For McQuay MDS Multi System Thoroughly check and clean the indoor and outdoor units; Clean or replace the air fil
-11-Design & installation Guide For McQuay MDS Multi SystemTr aditional air conditioning systemTr aditionalinverter systemMDS systemDigital com
the heat exchanger. If the unit is operating in an oily, salty, wet or dirty environment, do cleanit with special-purpose detergent. It is not advised
Fault codes here refer to the codes that appear on the remote control. If a host computer is available,the fault cause is directly displayed.7.1 Fault
-112-Design & installation Guide For McQuay MDS Multi System7.2 Indoor Unit Malfunction Code7.4 The Following Phenomena Are Not Unit Malfunctions:
-113-Design & installation Guide For McQuay MDS Multi SystemCHAPTERAnnexesAnnex 1(1) Parameters designed for various kinds of buildings
-114-Design & installation Guide For McQuay MDS Multi SystemAnnex 3 Table of recommended wind speeds for central air-conditioningAnnex 4 Criteria
-115-Design & installation Guide For McQuay MDS Multi System1. Use the Confirmation table to add more secondary refrigerant Calculate the addition
EN0601-500-APrinted in ChinaWWW.MCQUAY.COM
-12-Design & installation Guide For McQuay MDS Multi System Indoor unit: Ceiling exposed/floor standing unit1.3.7 Space Saving Compared to tradi
-13-Design & installation Guide For McQuay MDS Multi System Indoor unit: ceiling concealed unit Hot water heater box Electric heater box08-15 mean
-14-Design & installation Guide For McQuay MDS Multi System1.5 Products Series1.5.1 Outdoor UnitCapacity range3HP 4HP 5HP 6HP 8HP 10HP 12HP 15HP 1
-15-Design & installation Guide For McQuay MDS Multi System1.6 Performance Parameter1.6.1 Ceiling Concealed1.5.2 Indoor ProductsNotes: The nominal
-16-Design & installation Guide For McQuay MDS Multi SystemNotes: The nominal cooling capacity is gotten in the return air temperature of 27 /19 ,
-17-Design & installation Guide For McQuay MDS Multi SystemNotes: The nominal cooling capacity is gotten in the return air temperature of 27 /19 ,
-18-Design & installation Guide For McQuay MDS Multi System1.6.7 MDS-B Specification (Outdoor Unit)ModelMDS MDS MDS MDS MDS MDS MDS MDS MDS MDS MD
-19-Design & installation Guide For McQuay MDS Multi System1.7 Operating RangeNote The table is gotten based on the equivalent length of 16m and t
c 2004 McQuay International. All Rights Reserved. is a registered trademark of McQuay in the United States and other countries, licensed and recogn
-20-Design & installation Guide For McQuay MDS Multi System1.8.2 C TypeUnit: mmType: MDS-C1Type: MDS-Y5Unit: mm
-21-Design & installation Guide For McQuay MDS Multi System1.9 Outline of Indoor Units1.9.1 MCK010 050TLMJHBDACFEGKTOD ͺ9.720480 8080OD ͺ12.9OD ͺ1
-22-Design & installation Guide For McQuay MDS Multi System1.9.2 MDB050T3503408237021063103299895799512306-11.5x2030228682357910801771731.9.3 MD
-23-Design & installation Guide For McQuay MDS Multi System1.9.4 MCC008 010 015 018 020 025 030 040 050 060T1.9.5 MCM020T MCM030T MCM050TABCDEFGH
-24-Design & installation Guide For McQuay MDS Multi System1.9.6 Auxiliary Heating Coil Model A B C DHWT08-15 762 704 732 818HWT18-30 1022 964 9
-25-Design & installation Guide For McQuay MDS Multi System1.10 Outline of Outdoor Units1.10.1 MDS030A(R)1.10.2 MDS040A(R) MDS050A(R) MDS060A(R)Un
-26-Design & installation Guide For McQuay MDS Multi System1.10.3 MDS080B(R) MDS100B(R) MDS120B(R) MDS150B(R)B452651575AAmplify here A-AA-A8-14x20
-27-Design & installation Guide For McQuay MDS Multi SystemCHAPTER2Unit Control2.1 Introduction to the ControllerMDS system is controlled by the m
-28-Design & installation Guide For McQuay MDS Multi System2.3 Operation of the Controller2.3.1 Main FeaturesBoth wired controller (using the key
-29-Design & installation Guide For McQuay MDS Multi System Temp unit settingThere is a switch on the PCB board. When switch OP1 is ON, the unit i
CONTENTS1. Overview1.1 General Information ...41
-30-Design & installation Guide For McQuay MDS Multi System Timer settingPressTimer to enter timer setting (When the unit is ON, it can only be
-31-Design & installation Guide For McQuay MDS Multi System2.3.3 Wire Control Panel2.3.4 Outline and Dimension2.3.5 Installation Type concealed in
-32-Design & installation Guide For McQuay MDS Multi System2.4 Software Management System2.4.1 Real-time Monitor Software System monitoring softwa
-33-Design & installation Guide For McQuay MDS Multi System2.4.2 User-specific Biller McQuay launches the user-specific billing software basedon
-34-Design & installation Guide For McQuay MDS Multi System2.5 Network Central Control One outdoor unit can be connected with maximum 48 indoor un
-35-Design & installation Guide For McQuay MDS Multi System2.6 Wiring Diagram2.6.1 Wiring Diagram of Indoor Units Model MCC008/010/015/018/020
-36-Design & installation Guide For McQuay MDS Multi System Model MCK025/030/040/050TOFFONONOFFOFFONONONONTR1 TR2(220V~/50Hz)NONOFFOFF OFF OFFONOF
-37-Design & installation Guide For McQuay MDS Multi System Model MCM050T Model MDB050/060TOFFONOFF OFFHFLFMFOFFOFFTR1 TR2(220V~/50Hz)0NOFFJP1OFFS
-38-Design & installation Guide For McQuay MDS Multi System2.6.2 Wiring Diagram of Outdoor Units Model MDS030AMcQuayBGNDAAI-INHPLPOV-COMP1OV-COMP2
-39-Design & installation Guide For McQuay MDS Multi System Model MDS040AR Model MDS040AMcQuayBGNDAAI-INHPLPOV-COMP1OV-COMP2OV-COMP3NEUTRALNEUTRAL
-4-Design & installation Guide For McQuay MDS Multi SystemThe MDS(Multi Digital Scroll) air conditioning system is operated by a digital compresso
-40-Design & installation Guide For McQuay MDS Multi System Model MDS050A Model MDS050AR(220V~/50Hz)BGNDAAI-INHPLPOV-COMP1OV-COMP2OV-COMP3NEUTRALN
-41-Design & installation Guide For McQuay MDS Multi System Model MDS050AR(380V/3N~/50Hz) Model MDS060ABGNDAAI-INMcQuayHPLPOV-COMP1OV-COMP2OV-COMP
-42-Design & installation Guide For McQuay MDS Multi System Model MDS060AR(220V~/50Hz) Model MDS060AR(380V/3N~/50Hz)HPLPOV-COMP1OV-COMP2OV-COMP3NE
-43-Design & installation Guide For McQuay MDS Multi System Model MDS080/100/120B Model MDS080/100/120BRHI-U321LPTLOW-UAinApcBpcBinS2 S3S1MDS-MMDS
-44-Design & installation Guide For McQuay MDS Multi System Model MDS150B Model MDS150BR23HPT3121LPTHI-ULOW-UAinApcBpc BinS2 S3S1MDS-M~MMDS-P~M~MM
-45-Design & installation Guide For McQuay MDS Multi System Model MDS180B Model MDS180BR3121LPT3HPT2LOW-UHI-UAinApc BinBpcMDS-E~MM~MDS-MMDS-PS3S1
-46-Design & installation Guide For McQuay MDS Multi System Model MDS200/220/240B Model MDS200/220/240BR3121LPT3HPT2LOW-UHI-UMDS-E~M~MM~MDS-MMDS-P
-47-Design & installation Guide For McQuay MDS Multi System Model MDS260BR(Master Unit)2HPT331LPT12HI-ULOW-UAinApcBpcBinMDS-MMDS-PS3S1 S2~M~MM~HPT
-48-Design & installation Guide For McQuay MDS Multi System Model MDS260/280/300BR(Slave Unit)2HPT331LPT12HI-ULOW-UAinBinApcBpc~MMDS-MMDS-PS3S1 S2
-49-Design & installation Guide For McQuay MDS Multi SystemOutdoor220V/1~/50HzQFCommunication wireCommunication wire Communication wireMain power
-5-Design & installation Guide For McQuay MDS Multi SystemPWM valve power offValve closeFixed scroll move downwardsTwo scrolls gather togetherLoad
-50-Design & installation Guide For McQuay MDS Multi System2.7.3 MDS080 240B/BRBABAJ2BABinApcAinBpcConnecting central control(optional)BinApcABpcR
-51-Design & installation Guide For McQuay MDS Multi SystemNote: All the wiring should be fixed; Electric wiring must not touch the refrigerant pi
-52-Design & installation Guide For McQuay MDS Multi System SelectionCHAPTER33.1 Load Calculation3.1.1 Planning and Cooperation McQuay recommen
-53-Design & installation Guide For McQuay MDS Multi System If we know the heat performance index qv[W/(m3 . )] and outside volume V (m3), we can
-54-Design & installation Guide For McQuay MDS Multi System3.2 Selection of Indoor Units The selection of indoor unit should be based on the sever
-55-Design & installation Guide For McQuay MDS Multi System3.3 Selection of Outdoor UnitsFor the allowed combinations, please refer to the "T
-56-Design & installation Guide For McQuay MDS Multi System3.3.7 Actual Capacity Calculation Based on the model and combination rate of the outdoo
-57-Design & installation Guide For McQuay MDS Multi System270.650.600.700.800.900.95Correction factor 1.001.051.101.15262422201816141210-15-10-50
-58-Design & installation Guide For McQuay MDS Multi System3.4 Design of Air SystemThe air cooled pipeline unit is an important and complex part o
-59-Design & installation Guide For McQuay MDS Multi System3.4.2 Calculation of the Air Pipe ResistanceThe air resistance in the air outlet and re
-6-Design & installation Guide For McQuay MDS Multi SystemFour-way valveOutdoorFilter FilterElectronic expansion valveFilterFilterPWMLPSHPSCooling
-60-Design & installation Guide For McQuay MDS Multi SystemSpecifications of the rectangle air pipeUnit: mmSide size of the air pipe120 320 800 20
-61-Design & installation Guide For McQuay MDS Multi System Reinforcement of the air pipeGenerally, the air pipe is reinforced through using the r
-62-Design & installation Guide For McQuay MDS Multi SystemAcceptable (CO2) density Room typeAcceptable CO2 densityL/m3g/kg Place where pe
-63-Design & installation Guide For McQuay MDS Multi System3.5 Slection of Refnet Joint3.5.1 Copper Pipe Selection ( MDS100BR ) Diameter of the ma
-64-Design & installation Guide For McQuay MDS Multi SystemThe following tables show the refrigerant copper pipe dimension specifications.For MDS-
-65-Design & installation Guide For McQuay MDS Multi SystemUnit: mmRefnet joint type selection Y typeType: MDS-Y5Unit: mmRefnetLength (mm) Diam
-66-Design & installation Guide For McQuay MDS Multi SystemOD ͺ9.720480 8080OD ͺ12.9OD ͺ16.1OD ͺ19.3250550EDCBARefnet joint type ͺ(mm)Refnet join
-67-Design & installation Guide For McQuay MDS Multi SystemInstallationCHAPTER44.1 Outdoor Unit Installation To choose location of installationTo
-68-Design & installation Guide For McQuay MDS Multi System Handling outdoor unitsPlease refer to the followings to move units; To use 4 supportin
-69-Design & installation Guide For McQuay MDS Multi SystemInstallation of the Combined Outdoor Units (Suitable for Model of MDS260/280/300)Two ou
-7-Design & installation Guide For McQuay MDS Multi SystemMDS080BR MDS100BR MDS120BRFour-way valveHigh pressure switchStandard compressorElectron
-70-Design & installation Guide For McQuay MDS Multi System Balance pipe connection Balance pipe must be installed. Balance pipe shall be connecte
-71-Design & installation Guide For McQuay MDS Multi System10mmdrain direction Notes:a. Ensure piping and air duct working are most efficent lengt
-72-Design & installation Guide For McQuay MDS Multi SystemDuct Working Installation Air supply duct working installationTwo types of air supply d
-73-Design & installation Guide For McQuay MDS Multi Systemgood setting bad settingcool airflowcool airflowindoor unitceilingceilingj. To cut the
-74-Design & installation Guide For McQuay MDS Multi System Notes:Do not close all air outlets of indoor unit in the using of the unit to avoid th
-75-Design & installation Guide For McQuay MDS Multi System Installation of MDB-T series indoor unitTo mount the MDS050~060T in ceiling. As the ai
-76-Design & installation Guide For McQuay MDS Multi SystemInstallation of MCM-T Series Indoor UnitTo Check the Accessories are Ready To install t
-77-Design & installation Guide For McQuay MDS Multi System2. To fix the suspending panel with screw bolt as shown as above right figure.3. To han
-78-Design & installation Guide For McQuay MDS Multi System4.3 Refrigerant Piping Design and Installation4.3.1 Refrigerant Piping Design ( Includi
-79-Design & installation Guide For McQuay MDS Multi System Equivalent length Equivalent length = actual pipe length + number of elbows X equivale
-8-Design & installation Guide For McQuay MDS Multi SystemMDS200BR MDS220BR MDS240BROil crockHigh pressure sensorElectronic expansion valveFilterL
-80-Design & installation Guide For McQuay MDS Multi SystemOnly connected by the refnet jointOutdoor unitDistributor kitIndoor unitcontroller Conn
-81-Design & installation Guide For McQuay MDS Multi System Refrigerant Piping Installation: Refrigerant piping should use the appointed diameter
-82-Design & installation Guide For McQuay MDS Multi System4.3.2 Refrigerant Piping Assembly ProcessThree principle of the refrigerant piping asse
-83-Design & installation Guide For McQuay MDS Multi System4.3.3 Exchange Way of Nitrogen Gas (When Welding Copper Tube)Suppose no nitrogen gas is
-84-Design & installation Guide For McQuay MDS Multi SystemPipe inlet sealedOutdoor IndoorSpare pipeneeds to be sealed4.3.4 Transportation and C
-85-Design & installation Guide For McQuay MDS Multi System Steps: Put the pressure adjustor on the nitrogen bottle Connect the pressure adjustor
-86-Design & installation Guide For McQuay MDS Multi System4.3.7 Process Sequence of Air Leakage Test Main points of testingPlease test as follows
-87-Design & installation Guide For McQuay MDS Multi System4.3.8 Air Leak Gap Checking Test 1 (when the pressure reduces) Hearing use your ear t
-88-Design & installation Guide For McQuay MDS Multi SystemPipe size Thickness of the insulation material6.4mm~25.4mm 10mm or more28.6mm~38.1mm 15
-89-Design & installation Guide For McQuay MDS Multi SystemOuter diameter size Unit: mmOuter diameter sizeOuter diameterOuter diameterMetric syst
-9-Design & installation Guide For McQuay MDS Multi SystemMaster unitSlave unitHigh pressure sensorFilterFilterLow pressure sensorPressure tapping
-90-Design & installation Guide For McQuay MDS Multi System4.3.11 Refrigerant charging Calculation of the additional amount of the refrigerantAddi
-91-Design & installation Guide For McQuay MDS Multi SystemWater boiling point(c) Pressure(mmHg) Vacuity(mmHg)40 55 -70530 36 -72426.7 25 -73524.4
-92-Design & installation Guide For McQuay MDS Multi System Sequence of vacuum dryingAccording to the different ambient, vacuum drying has two way
-93-Design & installation Guide For McQuay MDS Multi System Special vacuum drying This vacuum drying way is used when there are some moisture in
-94-Design & installation Guide For McQuay MDS Multi System4.4 Design, Processing and Installation of Condensated Drain Pipe4.4.1 Design of Conden
-95-Design & installation Guide For McQuay MDS Multi System4.4.2 Making and Mounting Condensate Pipes4.4.3 Slope and Supporter of Condensate Pipe
-96-Design & installation Guide For McQuay MDS Multi System4.4.5 The Main Drainage Pipe of Multiple Indoor Units The pipe should be mounted from t
-97-Design & installation Guide For McQuay MDS Multi System4.4.8 Installation of the Drainage Lift PipeIf the water collecting header is installed
-98-Design & installation Guide For McQuay MDS Multi SystemTestingCHAPTER55.1 Hardware Diagram and Configuration5.1.1 MDS Series Indoor UnitsThe i
-99-Design & installation Guide For McQuay MDS Multi SystemAddress settings (SW2.1___SW2.6) Unit address SW2.1 SW2.2 SW2.3 SW2.4 SW2.5 SW2.600000